Search results for "System protection"
showing 9 items of 9 documents
A Method to Evaluate Voltages to Earth During an Earth Fault in an HV Network in a System of Interconnected Earth Electrodes of MV/LV Substations
2008
An easy and swift method to evaluate, in a system of interconnected earth electrodes, earth potentials on earthing systems of medium-voltage/low-voltage (MV/LV) substations, in an event of single-line-to-earth fault inside a high-voltage/medium- voltage (HV/MV) station, is presented. The advantage of the method is the simplicity of the mathematical model for solving complex systems of any size with a sufficient accuracy for practical purposes. This paper shows the results of simulations, performed on networks with different extensions and characteristics, organized in easy-to-read graphs and tables. A comparison of these results with the values obtained according to the procedure explained …
A New Solution for Low-Voltage Distributed Generation Interface Protection System
2015
In this paper, a new solution is proposed for the remote monitoring and control of distributed generators (DGs) and energy storage systems (ESSs) connected to low-voltage distribution networks. The proposed system fulfills the in-force standard requirements for the connection of DGs to the utility grid. Moreover, it allows implementing some enhanced functions for the remote control of inverters of DGs and ESSs, not only in terms of disconnection but also in terms of voltage regulation and power shuttering. The proposed solution is based on a new interface protection system and a dedicated secondary substation concentrator, which allows the communication between the distributed system operat…
Control of solid-state fault current limiter for DG-integrated distribution systems
2017
Fault current limier (FCL) is a device that limits the system current under fault conditions without disconnecting the system and affecting the power system protection components such as circuit breakers. Many types of FCLs have been proposed to limit the magnitude of the fault current. Solid-state fault current limiters (SSFCLs) can limit the peak value of the fault current by applying several methods, such as controlling the system impedance or controlling the voltage that appears across the fault. In this paper, a new control scheme for the SSFCL circuit is presented. The control method is based on controlling the duty cycle of solid state switches to control the rms value of the system …
Investigating the effect of distributed generators on traditional protection in radial distribution systems
2013
The recent changes in power network structure, development in green energy technologies and increased attention on environmental concerns have led to increase the installation of renewable energy based distributed generations (DG) in distribution networks. The increasing penetration of distributed generation in the distribution power system creates new technical and economical challenges; protection is one important topic of these challenges. High penetration of DG will have unfavorable impact on the traditional protection methods; the impact depends on the number, location and size of injected DG. To ensure safe and selective protection devices coordination, the impact of DG should be take…
Applications of the Fault Decoupling Device to Improve the Operation of LV Distribution Networks
2008
The aim of this paper is to present the operating principle of a new resonant device, called the fault decoupling device (FDD), able to improve power quality in electrical distribution systems. In low-voltage networks, this device can be employed in order to mitigate voltage dips due to faults or large induction motor startup. Moreover, in the presence of distributed-generation (DG) units, the FDD allows one to obtain various benefits such as a reduction of the fault current in each node of the network and an increase in the voltage at the DG unit node. In order to show the performances of the FDD, analytical studies and computer simulations were carried out which took into account various …
Verifying the effect of distributed generators on voltage profile, power losses and protection system in radial distribution networks
2013
In the recent years the electrical power networks are undergoing rapid restructuring and developing process worldwide. Advancement in technologies and concern about the environmental impacts have led to increase interconnection of renewable energy based distributed generations (DGs) in distribution networks. The DGs have significant impacts on the distribution systems; these impacts may be either positively or negatively depending on the modified interconnected DG distribution network structure. It will be necessary to consider many issues concerning these impacts. In this paper, an investigation of DGs impacts on voltage profile, power losses, and protection system in radial distribution n…
An analysis methodology to evaluate the contribution to electrical security given by bare buried conductors in a system of intertied earthing grids
2004
The paper presents an analysis methodology for a single-line-to-ground fault, occurring at a secondary MV/LV substation in a power network formed by a HV/MV station, feeding, through a MV tri-phase cable line, N MV/LV substations whose earth electrodes are interconnected by bare buried conductors. In the preliminary explanation of the methodology, earth buried conductors are studied in their double function of earth electrodes and connection elements between earthing grids, both in absence and in presence of other interfering conductors. Subsequently analyzed is, with a distributed parameters approach, the system constituted by an earth buried conductor and a MV tri-phase cable line. The eq…
UPS fuel cell based: An innovative back-up system
2007
The aim of the paper is to evaluate the technical feasibility and aspects related to the use, in an Uninterruptible Power Supply (UPS), of fuel cells instead of traditional electrochemical batteries. The proposed system, named UPS-FCB (Fuel Cell Based) presents a modular and versatile system configuration; particularly it is possible to integrate it with traditional UPS. Moreover the system features can be modified in terms of power, reliability, back-up time, etc., by changing the power devices. A detailed experimental analysis has been carried out on a passive stand-by UPS integrated with a FCB; experimental results can be easily extended to the other possible system architectures. © 2007…
Integration Issues of Distributed Generators Considering Faults in Electrical Distribution Networks
2014
In the recent years there is a great interest in integration of distributed generation (DG) units at distribution level; this integration leads to planning as well as operational challenges. Some possibilities to handle grid planning issues are addressed in this paper. Effects on grid protection, fault current level, and voltage profile are investigated and described for different types of DG units; the classification of DG units is based on their terminal characteristics in terms of real and reactive power delivering capability. Different scenarios for mis-coordination problems caused by DG interconnection are discussed. The effect of the DG on the voltage profile of a distribution network…